Schneider Electric TeSys D kontaktor-3P(3 NO) - AC-3 - <=440 V 32A- 110 V DC kalem ; LC1D32FD

Schneider Electric TeSys D kontaktor-3P(3 NO) - AC-3 - <=440 V 32A- 110 V DC kalem ; LC1D32FD

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 32 A - 110 V DC coil...

Brand: Schneider Electric
Product Code: LC1D32FD
Availability: Check availability
VAT-exclusive price: 15.569,00
VAT-inclusive price: 18.682,80

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 32 A - 110 V DC coil

Main
range
TeSys
 
product name
TeSys D
 
product or component type
Contactor
 
device short name
LC1D
 
contactor application
Resistive load
Motor control
 
utilisation category
AC-3
AC-4
AC-1
 
poles description
3P
 
power pole contact composition
3 NO
 
[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz
Power circuit: <= 300 V DC
 
[Ie] rated operational current
32 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
 
motor power kW
7.5 kW at 220...230 V AC 50/60 Hz (AC-3)
15 kW at 380...400 V AC 50/60 Hz (AC-3)
15 kW at 415...440 V AC 50/60 Hz (AC-3)
18.5 kW at 500 V AC 50/60 Hz (AC-3)
18.5 kW at 660...690 V AC 50/60 Hz (AC-3)
7.5 kW at 400 V AC 50/60 Hz (AC-4)
 
motor power HP (UL / CSA)
2 hp at 115 V AC 50/60 Hz for 1 phase motors
5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
10 hp at 230/240 V AC 50/60 Hz for 3 phases motors
20 hp at 460/480 V AC 50/60 Hz for 3 phases motors
30 hp at 575/600 V AC 50/60 Hz for 3 phases motors
 
control circuit type
DC standard
 
[Uc] control circuit voltage
110 V DC
 
auxiliary contact composition
1 NO + 1 NC
 
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
 
overvoltage category
III
 
[Ith] conventional free air thermal current
10 A (at 60 °C) for signalling circuit
50 A (at 60 °C) for power circuit
 
Irms rated making capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
550 A at 440 V for power circuit conforming to IEC 60947
 
rated breaking capacity
550 A at 440 V for power circuit conforming to IEC 60947
 
[Icw] rated short-time withstand current
260 A 40 °C - 10 s for power circuit
430 A 40 °C - 1 s for power circuit
60 A 40 °C - 10 min for power circuit
138 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
 
associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-1
63 A gG at <= 690 V coordination type 1 for power circuit
63 A gG at <= 690 V coordination type 2 for power circuit
 
average impedance
2 mOhm - Ith 50 A 50 Hz for power circuit
 
[Ui] rated insulation voltage
Power circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
 
electrical durability
1.65 Mcycles 32 A AC-3 at Ue <= 440 V
1.4 Mcycles 50 A AC-1 at Ue <= 440 V
 
power dissipation per pole
2 W AC-3
5 W AC-1
 
Front cover
With
 
mounting support
Plate
Rail
 
standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
 
product certifications
GL
BV
CSA
DNV
LROS (Lloyds register of shipping)
CCC
RINA
GOST
UL
 
connections - terminals
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm²flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…10 mm²flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm²flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm²solid without cable end
Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²solid without cable end
 
tightening torque
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
 
operating time
53.55...72.45 ms closing
16...24 ms opening
 
safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
 
mechanical durability
30 Mcycles
 
maximum operating rate
3600 cyc/h 60 °C
 
Complementary
coil technology
Built-in bidirectional peak limiting diode suppressor
 
control circuit voltage limits
0.1...0.25 Uc (-40…70 °C):drop-out DC
0.7...1.25 Uc (-40…60 °C):operational DC
1...1.25 Uc (60…70 °C):operational DC
 
time constant
28 ms
 
inrush power in W
5.4 W (at 20 °C)
 
hold-in power consumption in W
5.4 W at 20 °C
 
auxiliary contacts type
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
 
signalling circuit frequency
25...400 Hz
 
minimum switching current
5 mA for signalling circuit
 
minimum switching voltage
17 V for signalling circuit
 
non-overlap time
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
 
insulation resistance
> 10 MOhm for signalling circuit
 
contact compatibility
M4
 
compatibility code
LC1D
 
Environment
IP degree of protection
IP20 front face conforming to IEC 60529
 
protective treatment
TH conforming to IEC 60068-2-30
 
pollution degree
3
 
ambient air temperature for operation
-40…60 °C
60…70 °C with derating
 
ambient air temperature for storage
-60…80 °C
 
operating altitude
0...3000 m
 
fire resistance
850 °C conforming to IEC 60695-2-1
 
flame retardance
V1 conforming to UL 94
 
mechanical robustness
Vibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 4 Gn, 5...300 Hz
Shocks contactor closed: 15 Gn for 11 ms
Shocks contactor open: 8 Gn for 11 ms
 
height
85 mm
 
width
45 mm
 
depth
101 mm
 
net weight
0.535 kg
 
Packing Units
Package 1 Weight
0.585 kg
 
Package 1 Height
0.500 dm
 
Package 1 width
0.920 dm
 
Package 1 Length
1.120 dm
 
Offer Sustainability
Sustainable offer status
Green Premium product
 
REACh Regulation  
REACh free of SVHC
Yes
 
EU RoHS Directive  
Toxic heavy metal free
Yes
 
Mercury free
Yes
 
RoHS exemption information  
China RoHS Regulation
China RoHS declaration
 Pro-active China RoHS declaration (out of China RoHS legal scope)
 
Environmental Disclosure  
Circularity Profile  
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
 
PVC free
Yes
 
Contractual warranty
Warranty
18 months

Similar products:


Schneider Electric TeSys D kontaktor - 3P(3 NO) - AC-3 - <= 440 V 18 A - 110 V DC kalem ; LC1D18FD

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 18 A - 110 V DC coil
-
Need to order

(Out of stock)

 
 
10.223,00

Schneider Electric TeSys D kontaktor - 3P(3 NO) - AC-3 - <= 440 V 25 A - 110 V DC kalem ; LC1D25FD

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A - 110 V DC coil
-
Need to order

(Out of stock)

 
 
12.848,00

Schneider Electric TeSys D kontaktor-3P(3 NO) - AC-3 - <=440 V 32A- 24 V DC kalem ; LC1D32BD

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 32 A - 24 V DC coil
-
Need to order

(Out of stock)

 
 
15.569,00

Schneider Electric TeSys D kontaktor-3P(3 NO) - AC-3 - <=440 V 32A- 48 V DC kalem ; LC1D32ED

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 32 A - 48 V DC coil
-
Need to order

(Out of stock)

 
 
15.781,00

Schneider Electric TeSys D kontaktor - 3P(3 NO) - AC-3 - <= 440 V 40 A - 110 V DC standardni kalem ; LC1D40AFD

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 40 A - 110 V DC standard coil
-
Need to order

(Out of stock)

Price on request

Schneider Electric TeSys D kontaktor - 3P(3 NO) - AC-3 - <= 440 V 50 A - 110 V DC standardni kalem ; LC1D50AFD

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 50 A - 110 V DC standard coil
-
Need to order

(Out of stock)

 
 
24.552,00

ELECTRO PNEUMATIC SOLUTIONS DOO

  • Jugoslovenska 2/13A, Čukarica, Beograd
  • Opening Times: Monday - Friday 8am-5pm
  • Telephone:
  • 011 257 1922
  • +381 64 659 66 55
  • +381 62 800 70 44
  • email: office@ep-solutions.rs

linkedin youtube instagram twitter facebook
1
2
3
Compare products Remove all products